1DESTINY 4100Installation InstructionsK1106-1 2/99

Seite 2

10Retainer Clip(Note Position)Retainer SlotLockedUnlockedControl BoardControl Board1. Remove the cabinet door2. Remove the lock knockout from the cont

Seite 3

11Wiring DiagramTo HousePhonesFrom PhoneCompanyGreenRJ-31XPLUGRedWhen using smoke reset, programthe Smoke Power Trigger to output8 (aux relay) 043,008

Seite 4 - Software Revisions

12Wiring NotesGrounding: In UL installations where the Speaker Supervision option is enabled, grounding is notpermitted.If grounding, it is recommende

Seite 5 - Table of Contents

13System TerminalsHouse Phones: The R1 and T1 terminals provide telephone service to the house if the installationcontains an RJ-31X terminal block fo

Seite 6 - Glossary

14Auxiliary Relay: A programmable relay is available on the "RC", "RNC" , and "RNO" terminals. Use "RC"for r

Seite 7 - Specifications

15there is a modem to modem connection during upload or download.POWER LED: At the top right of the board is a red LED labeled "POWER" which

Seite 8

16Two Resistor Supervision: This wiring arrangement allows the system to detect and handle open loops and shorts asa trouble condition. Through progr

Seite 9

17ProgrammingSystem options are contained in EEPROM. Each programmable section of memory has a 4 digit location and athree digit value. To reduce th

Seite 10 - Mounting the Control Board

18Quick StartKeypad connection: Connect a hardwire keypad to the keypad terminals on the control board, be certain toproperly match the colors as foll

Seite 11 - Wiring Diagram

19Using This Manual:Automated Locations: Automated Location prompt for specific information and automatically record theappropriate information into t

Seite 13 - System Terminals

20System SetupZone 1-8System KeypadsSystem Board Inputs 1-8Local Phone PanicTwo Wire Smoke LoopWireless TransmittersZone 9Zone 27Zones 24 - 25Zones 10

Seite 14

21Programming ZonesThe device types for each zone on the Destiny 4100 are predefined. The device assignments are fixed andmay not be modified.Zones

Seite 15

22Zones 1 - 8: System ControllerAt default, all 8 system inputs are disabled. To enable a hardware input, enter a zone type in the zone typelocation.

Seite 16

23=RQH,QSXW:LUH6PRNH2SWLRQ /RFDWLRQ 'HIDXOW 1HZ9DOXH 'HIDXOW'HVFULSWLRQ=RQH7\SH   :RUG :RUG :RUG :RUG2SWLRQ 

Seite 17 - Locations and Values

24=RQH =RQH,QSXW7UDQVPLWWHU6HULDO ,QSXW7UDQVPLWWHU6HULDO2SWLRQ /RFDWLRQ 'HIDXOW 1HZ9DOXH 2SWLRQ /RFDWLRQ 'HIDXOW 1HZ9DOXH&

Seite 18 - Quick Start

25Zones 18 - 23: Alarm Type Transmitters Continued=RQ H =R QH,QSXW7UDQVP LWWHU6HULDO ,QSXW7UDQVP LWWHU6HULDO2SWLRQ /RFDWLRQ 'HID

Seite 19 - Using This Manual:

26Portable TransmittersType Description Value5801...4 button portable...

Seite 20 - System Setup

27=RQH,QSXW6\VWHP.H\SDGV2SWLRQ /RFDWLRQ 'HIDXOW 1HZ9DOXH±6WDWXV  ±0RQLWRU  ±)  ±  ±  

Seite 21 - Zone Options 2

28Zone 29: Monitor Trouble ConditionsOption - A description of each option is available in the Glossary Location Value* Duration for recognition of A

Seite 22

29Automated Programming LocationsClear user codes 2-8...

Seite 23 - 5816 (MN) 5817

3Dear Dealer/Installer:We appreciate your decision to use the Destiny 4100 for this installation. As a division of the Pittway Corporationand member

Seite 24

30VocabularyWord LocationAccess...024Account...025Alarm...222Alert...026Am.

Seite 25

31System Times And Other OptionsSystem Time Options - A description of each time is available in the Glossary Units Location DefaultEntry delay 1 (Not

Seite 26 - 58045801

32User Code + Digit FunctionsUser Code + Options Local phone/keypads Function Remote Phone FunctionFunction for User Code + 1...

Seite 27 - Zone 27: Local Phone

33System Options - Group 4Options - Enter Total - A description of each option is available in the Glossary Location ValuePrevent access to Program M

Seite 28 - System Access Codes

34Extended Monitor Zone Type AssignmentZone Types - Enter Total for Extended Monitor A Location ValueExterior instant...

Seite 29 - Assigning Words to Zones

35Smoke Detector Low Battery WarningUpon detection of a low battery from a transmitting device assigned as a Fire zone type, the panel will start awar

Seite 30 - Vocabulary

36After the settling delay completes, the panel begins a window delay and startswatching for another on-board or 2-wire smoke zone trip. The period

Seite 31 - User Code Options

37Reporting FormatReporting Options: Enter total - See Glossary for a description of each format Location ValueSilent Knight Slow...

Seite 32 - System Options - Group 3

38Report CodesReport Type Location ValueExterior Instant Central Station Report Code...0337...003_______Dialer Option...

Seite 33

39Report Type Location ValueAC Fail Central Station Report Code...0365...008_______Dialer Option...

Seite 34

4Software RevisionsCurrent software at time of printing:Control Panel: 1.01Bridge (Gate): 1.03EXP8: 1.01LED Keypad: 4.01Downloader 1.001.00 To 1.01 Pa

Seite 35 - Smoke Verification

40Ademco Contact ID Report CodesAPEX Description Code Sent to Central Station ADEMCO DescriptionExterior instant...E 13

Seite 36 - Speaker (Bell) Supervision

41Automatic Communicator TestingChoose to Report Daily, Weekly, or Monthly and enter the appropriate value Location ValueReport Daily...

Seite 37 - Dialer Options

42Two-Way Voice OptionsThis feature is not permitted in a UL installationVoice Only Options - Enter total ValueOne Digit Access...

Seite 38 - Report Codes

43System TriggersEvent Location Output Location Option Location Time Option Default TimesAny alarm activation...0122.

Seite 39

44System Triggers OptionOption - Enter Total ValueActivation ActionDo Nothing...

Seite 40 -

45Glossary of TermsAccess code before arm: In this configuration, a full access code (arm/disarm code) must be entered to arm thesystem. Once armed,

Seite 41 - Two-Way Digit Assignments

46Button Functions: These are activations that are controlled by portable transmitters and/or keycombinations on keypads.Silence Day Zone: Cancels a

Seite 42 - Two-Way Voice Options

47Bypass Mode: To bypass individual zones, enter a valid full function code followed by the 9 digit.The system will speak "BYPASSED MODE, ENTER Z

Seite 43 - System Triggers

48Clear EML and LTM: The Event Memory Log and Long Term memory can be cleared by entering 9898while in program mode.Clear Keypad Status: Under very un

Seite 44 - System Triggers Option

49Display Open at Keypad: Used to show when specified zones are open. Typically, all internal zones (PIR's,Smoke Detectors) are not programmed t

Seite 45 - Glossary of Terms

5Table of ContentsSpecifications...7It

Seite 46

50Enable Two-way Callback:For this option to be used, at least one activation must be programmed to enable two-way voice/listen-in with the central st

Seite 47

51There are two different levels or types of extended monitor, A and B. Locations 0177and 0178 determine which zone types are to be monitored by each

Seite 48

52No Exterior Instant When enabled, this option will eliminate the exit delay on all exterior instant zonesExit Delay: following arming to either HOM

Seite 49

53Report Code: All events that initiate a communicator report are associated with a report code(based on zone type) that appears at the central statio

Seite 50

54Set Time and Date: After entering 9991 the system will prompt "Enter Eleven." The time, day, and dateare entered in the following format

Seite 51

55Speak Phone Number: To confirm programmed phone numbers, Enter the appropriate 9000 location and thenumber will be spoken. Special dialing feature c

Seite 52

56Touch Tone / This location determines the type phone service the panel uses for dialing. ProgramPulse Dial: 000 for touch-tone or 001 for rotary.Tr

Seite 53

57Disarm: Active when the panel is disarmed. The output is restored when the panel is armed.Access Code Entered: Output is activated when an access

Seite 54

58There are three security options associated with two-way callback, one digit access,full code access, and entering 0 to exit to keypad mode. If eit

Seite 55

59Zone type assignment: Auxiliary: Auxiliary zones are non-burglary zones designed to provide an automation,information, or service input to the syst

Seite 56

6Reporting Format...37Dialer Options...

Seite 57

60Interior Delay #2: Same as Exterior Delay #2 except active only in AWAY and NIGHT modeand no monitor is provided. Uses delay time #2.Panic: Panic

Seite 58

61This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires thefollowing statement for your informati

Seite 59

62Preparation of an evacuation plan Is of prime importance in fire prevention.Establish a household emergency evacuation plan in the event of fire. Re

Seite 60

63WARNINGTHE LIMITATIONS OF THIS ALARM SYSTEMWhile this System is an advanced wireless security system, it does not offer guaranteed protection agains

Seite 61

64ADEMCO LIMITED WARRANTYAlarm Device Manufacturing Company, a Division Of Pittway Corporation, and its divisions, subsidiaries and affiliates(`Seller

Seite 62 - INSTALLATION LAYOUT

7SpecificationsElectrical: Voltage Input: 16.5 VAC 40 VA from supplied transformerExternal Speaker: 10 Watt minimum, 8W horn type - Ademco 713 or equi

Seite 63

8Speaker Output: 10 Watt internal siren driver with full speech10 Watt external siren driver with full speechDesigned for use with 8W, 10 watt minimum

Seite 64 - ADEMCO LIMITED WARRANTY

9Items Included With the Control Panel:Please examine the contents of the shipping box for the following items:1 - Control Panel 1 - Lock, key, and re